Carel AL10 Error Code
Compressor 1 LP in heating (pressure switch) Comp. 1 OFF Automatic Settable* AL1
Source: 030221501.pdf
What does Carel AL10 mean?
AL10 on Carel µChiller and pCO chiller controllers signals that the low-pressure (LP) safety switch on compressor 1's heating circuit has tripped. In heat-pump mode, the LP switch monitors suction pressure on the heating cycle; if it drops too low, compressor 1 is shut down to prevent operation in a vapor-starved condition during low outdoor temperature heating operation.
Symptoms
- AL10 displayed on the Carel controller.
- Compressor 1 is shut down during heating operation.
- Suction pressure on compressor 1's circuit is at or below the LP cutout in heating mode.
- Alarm requires manual reset after diagnosis.
Common causes
- Outdoor ambient temperature too low for the heat pump's rated operating range.
- Refrigerant undercharge causing low suction pressure even in heating mode.
- Outdoor coil (acting as evaporator in heating mode) heavily iced over, blocking airflow.
- Outdoor fan motor failed, reducing airflow over the outdoor coil.
- LP switch cutout pressure set too high relative to low-ambient heating conditions.
Ask the AskWhiz AI about Carel AL10
AskWhiz
online
Diagnostic steps
Record the outdoor ambient temperature
Check the current outdoor temperature against the unit's rated minimum heating ambient. Operating below the minimum rating causes LP trips in heating mode.
Inspect the outdoor coil for ice
Check the outdoor coil for ice bridging or heavy frost that blocks airflow. Initiate a defrost cycle if icing is present and investigate why defrost did not clear it automatically.
Verify outdoor fan operation
Confirm the outdoor fan is running at correct speed. A failed fan motor starves the outdoor coil of airflow, dropping evaporating pressure in heating mode.
Connect refrigerant gauges and check suction pressure
Measure suction pressure on compressor 1's circuit in heating mode. Compare to expected saturation pressure for the current outdoor temperature.
Reset the alarm after correction
After addressing the identified cause, reset AL10 at the controller and monitor the system through a full heating cycle.
When to call a professional
Call a licensed refrigeration/heat pump engineer for refrigerant handling, recharge, LP switch replacement, or investigation of LP trips occurring at ambient temperatures within the unit's rated operating range. These indicate refrigerant circuit or control faults that are unsafe to diagnose without proper tools and F-Gas certification.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.carel.com