Quick Answer
GEA industrial refrigeration plants — Grasso screw packages and GEA Bock semi-hermetic compressors on ammonia (R717) or CO2 (R744) — run on Omni unit controllers. Common faults: high discharge temperature, oil flow / differential pressure trips, motor protection (Mp / INT69), HP / LP cutouts and ammonia leak alarms. Identify root cause before resetting any safety device.
GEA Troubleshooting Assistant
Get instant AI-powered help for GEA fault codes and equipment issues via WhatsApp. Our assistant is trained on official manufacturer documentation — available 24/7 for field technicians.
Co-founder & CEO · Reviewed May 2026
What error codes does GEA display?
High discharge temperature on Grasso screw — check liquid injection, oil cooler flow and condensing pressure
Oil differential pressure below 2.5–4.5 bar above suction — check oil filter, pump prelube and oil level
Oil filter differential pressure high — replace filter element at 0.8–1.0 bar dP
Motor protection (INT69 / INT389) PTC trip on Bock — cool 30–60 min, verify phases and FLA before reset
High-pressure cutout (typical NH3: 17–18 barg) — check condenser fouling, fan failure, non-condensables
Low-pressure cutout — check refrigerant charge, plugged liquid line and closed solenoid valves
Ammonia gas detection alarm — verify with handheld detector, ventilate per IIAR / EN 378 before reset
Discharge pressure high warning — inspect condenser water flow, fan operation and purge non-condensables
Low or high suction superheat — check expansion valve, evaporator load and economiser sequence
Omni controller communication loss to slide-valve actuator or VFD — check network cable, terminations and addresses