Quick Answer
Lochinvar gas boilers and water heaters — KNIGHT (commercial), CREST (high-efficiency), Crest CFC (combi), Armor, Shield, Hellcat, and FTXL — use a two-tier alert hierarchy on the SMART SYSTEM display. Lockout faults (No Flame Ign, APS Open, Manual Reset High Limit, Sensor Open / Shorted, Flame Sequence, GV/Relay Fail) require manual reset; warnings or blocking codes self-clear when the condition resolves. Fuses F1–F5 on the control board protect specific circuits. Knight commercial boilers add F-numbered fault codes (F213, F303) for combustion-air, ignition, and pressure faults.
Lochinvar Troubleshooting Assistant
Get instant AI-powered help for Lochinvar fault codes and equipment issues via WhatsApp. Our assistant is trained on official manufacturer documentation — available 24/7 for field technicians.
Co-founder & CTO · Reviewed May 2026
What error codes does Lochinvar display?
Ignition failure after four attempts — inspect electrode, gas pressure, and 24 VAC at valve
Air pressure switch contacts open — vent length, intake blockage, or switch failure
Outlet temperature exceeded fixed limit — check pump operation and water flow
Inlet or outlet water sensor disconnected — inspect wiring and resistance
Inlet or outlet sensor shorted — measure against Table 3B resistance values
Flame signal detected with no call — supply voltage, flame rod, or board fault
Gas-valve circuit not detected — check 2-pin connector and wiring harness
Relay-board / 24 V DC supply fuse open — inspect for shorts on the relay rail
24 V control-circuit fuse (3.15 A slow-blow) blown — unit goes non-responsive
Main control board logic fuse (1.25 A slow-blow) blown — display blank, no indicators