AHT Cooling Systems E38 Error Code
E39 E40 E41 Temperatura de controlo demasiado alta Falha no tempo de execucao no
Source: vento-spi__aht-vento-iom.pdf
What does AHT Cooling Systems E38 mean?
The controller reports that the control temperature has exceeded its permitted upper alarm threshold. This is distinct from E35 (goods room temperature too high) — E38 monitors a specific control reference point used by the regulation loop. When the control temperature rises above its maximum permitted value, E38 triggers to alert staff to a loss of cooling performance before goods are critically damaged.
Symptoms
- E38 fault code displayed with red LED and buzzer active.
- Control temperature reading above the configured high-temperature alarm threshold.
- Cabinet may be running but unable to achieve adequate cooling.
- Goods inside may be at elevated temperatures — product spoilage risk increases with time.
- Compressor may be running continuously without reducing the control temperature.
Common causes
- Condenser coils dirty or blocked, severely reducing heat rejection and causing high return temperatures.
- Compressor not running due to a safety trip (check for co-existing fault codes).
- Refrigerant loss reducing cooling capacity — compressor runs but cannot lower temperatures.
- Excessive store ambient temperature limiting condenser performance beyond the cabinet's rated ambient class.
- Night blind or air curtain fault allowing excessive warm air infiltration into the goods space.
- Control sensor failed or mislocated, producing a falsely high reading.
Ask the AskWhiz AI about AHT Cooling Systems E38
AskWhiz
online
Diagnostic steps
Protect goods immediately
Transfer temperature-sensitive goods to another correctly rated cabinet before product temperatures reach unsafe levels.
Check for co-existing fault codes
Review the display for other active fault codes (e.g. compressor safety chain E07, high-pressure E06, or high condensation pressure E43) that would explain why the cabinet cannot cool.
Inspect condenser coils and ventilation
Check condenser coils and air intake/exhaust grilles for dust and blockage. Clean the condenser per the AHT cleaning procedure if fouled. Ensure at least 60 mm clearance above the cabinet for warm air exhaust.
Verify store ambient temperature
Confirm the store temperature is within the rated ambient class for the device. High store temperatures — especially during summer — can push the cabinet beyond its rated performance envelope.
Check control sensor
Inspect the control temperature sensor for correct mounting and wiring. Test sensor resistance with a multimeter at ambient temperature and compare to the NTC reference curve to confirm or rule out a sensor fault.
Contact AHT service
If the control temperature alarm is not caused by condenser fouling or ambient overtemperature, contact AHT service at 00800/73783248 or www.aht.at/service for refrigerant or compressor diagnosis.
When to call a professional
If E38 persists after condenser cleaning and ambient checks, an AHT-authorized technician is required to diagnose refrigerant charge, compressor health, or sensor faults. Contact AHT service at 00800/73783248 or www.aht.at/service.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official AHT Cooling Systems documentation and can diagnose this fault code and guide you through the repair in minutes.
5 free questions per bot in your browser — no signup.
Other AHT Cooling Systems Error Codes
Fault in electronic expansion valve E01 Fault in suction pressure sensor E02 Fau
Fault in air intake sensor E04 Fault in air outlet sensor E05 Fault in slat sens
Fault in high-pressure sensor E07 Fault in compressor safety chain E08 Fault in
Fault in internal temperature sensor (Goods room) E10 Supply voltage too low/too
Low battery voltage (see → Chapter 10.2.3) E12 Fault in software class B (safety
Fault in EEPROM (control board defective) E32 Suction pressure too low E33 Super
Superheating too high E35 Internal temperature too high (goods room) E36 Interna
Control temperature too low E38 Control temperature too high E39 Run-time fault
Fault in internal memory E41 Heating gas temperature too high (pressure tube sen
Time-out Valve opening 100% E43 Condensation pressure too high E44 External alar
E03 E04 E05 E06 E07 Falha no sensor de temperatura do gas de succao (sensor do c
compressor Falha no sensor de temperatura do pressao) E10 E09 gas térmico (senso
Sources: www.aht.at
AskWhiz Playground
Test your diagnostic skills
Play a real HVAC service call in the AskWhiz Playground — real brands, real fault codes, no signup.
Play a real service call