AHT Cooling Systems E43
Zu hoher Kondensationsdruck E44 Externer Alarm
Source: vento-spi__aht-vento-iom.pdf
What does AHT Cooling Systems E43 mean?
The controller reports that condensation pressure is too high. The high-pressure sensor (monitored under E06) has measured a condensing pressure above the configured alarm threshold. High condensation pressure reduces compressor efficiency, increases discharge temperature, and — if left uncorrected — will eventually trip the mechanical high-pressure cut-out and shut the compressor down. E43 is the controller's early warning before a full compressor safety trip (E07).
Symptoms
- E43 fault code displayed with red LED and buzzer active.
- Condensation pressure reading above the high-pressure alarm threshold.
- Compressor may still be running but under stress — discharge line will be very hot.
- Cabinet cooling capacity reduced — goods room temperature may begin rising.
- High-pressure mechanical cut-out (E07) may follow if condition is not corrected.
Common causes
- Condenser coils dirty or blocked with dust and grease, severely restricting heat rejection.
- Condenser air discharge obstructed — objects placed on top of or against the cabinet blocking warm air exhaust.
- Store ambient temperature too high, reducing the temperature differential between refrigerant and room air.
- Condenser fan motor failed or running slowly, reducing airflow across the condenser.
- Refrigerant overcharge causing excessively high condensing pressure at normal ambient conditions.
- High-pressure sensor fault producing false high readings (check against mechanical gauge if available).
Diagnostic steps
- 01
Check and clear condenser
Inspect condenser coils and grilles for dust and debris. Clean the condenser per the AHT Vento cleaning procedure — this is the most common cause of high condensation pressure and can often resolve E43 immediately.
- 02
Ensure adequate ventilation around the cabinet
Verify that there is at least 60 mm clear space above the cabinet for warm air exhaust. Remove any objects, signs, or obstructions placed on top of or blocking condenser airflow.
- 03
Check condenser fan operation
Confirm the condenser fan is running at normal speed. A failed or slow fan significantly reduces heat rejection. Listen for unusual noise and feel for airflow at the condenser discharge.
- 04
Verify ambient temperature
Check that the store temperature is within the rated ambient class for the device. High ambient temperatures above the cabinet's rated maximum will elevate condensing pressure.
- 05
Monitor pressure after corrective action
After cleaning the condenser and removing obstructions, allow the cabinet 30 minutes to stabilize. If E43 clears and stays clear, the fault was condenser-related.
- 06
Contact AHT service if E43 persists
If condensation pressure remains high after cleaning and ventilation checks, contact AHT service at 00800/73783248 or www.aht.at/service. Refrigerant charge assessment, fan replacement, or sensor replacement requires an authorized technician.
Keep this fix — get it by email with every AHT Cooling Systems error code
A clean printable version of this AHT Cooling Systems E43 guide + the full AHT Cooling Systems code pack (25 codes), straight to your inbox. Free.
When to call a professional
If E43 persists after condenser cleaning and airflow checks, an AHT-authorized technician is required to assess refrigerant charge, condenser fan, and high-pressure sensor. On R-290 units, all refrigerant circuit work requires flammable-refrigerant certified personnel. Contact AHT service at 00800/73783248 or www.aht.at/service.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther AHT Cooling Systems error codes
Fault in electronic expansion valve E01 Fault in suction pressure sensor E02 Fau
E03Fault in air intake sensor E04 Fault in air outlet sensor E05 Fault in slat sens
E06Fault in high-pressure sensor E07 Fault in compressor safety chain E08 Fault in
E09Fault in internal temperature sensor (Goods room) E10 Supply voltage too low/too
E11Low battery voltage (see → Chapter 10.2.3) E12 Fault in software class B (safety
E13Fault in EEPROM (control board defective) E32 Suction pressure too low E33 Super
E34Superheating too high E35 Internal temperature too high (goods room) E36 Interna
E37Control temperature too low E38 Control temperature too high E39 Run-time fault
E40Fault in internal memory E41 Heating gas temperature too high (pressure tube sen
E42Time-out Valve opening 100% E43 Condensation pressure too high E44 External alar
E02E03 E04 E05 E06 E07 Falha no sensor de temperatura do gas de succao (sensor do c
E08compressor Falha no sensor de temperatura do pressao) E10 E09 gas térmico (senso
Sources: www.aht.at