Quick Answer
Dixell (now Copeland after the 2024 Emerson rebrand) refrigeration controllers use P1–P3 for Pb1 / Pb2 / Pb3 probe faults, HA / LA for high / low temperature alarms, EA for external safety inputs, CA for door-open, and nP for no-probe. iChill chillers (IC100CX) add AL01–AL77; XWi70K reports E11–E14 / E21–E24 for Embraco compressor faults.
Dixell/Copeland Troubleshooting Assistant
Get instant AI-powered help for Dixell/Copeland fault codes and equipment issues via WhatsApp. Our assistant is trained on official manufacturer documentation — available 24/7 for field technicians.
Co-founder & CEO · Reviewed May 2026
What error codes does Dixell/Copeland display?
Probe Pb1 (cabinet) fault — verify NTC 103AT-2, ohm probe (10 kΩ at 25 °C), replace if open / shorted
Probe Pb2 (evaporator / defrost) fault — defrost terminates by MdF time-out only, replace probe
Probe Pb3 (condenser) fault — disables HA2 / LA2 condenser alarms, check AP3 allocation
High temperature alarm on Pb1 — inspect condenser, door seal, ALU threshold and AFH differential
Low temperature alarm on Pb1 — verify ALL threshold and probe placement, auto-reset
External alarm — digital input EAL active, check i1P polarity and field safety device
Door / compressor digital-input alarm — door held open beyond OAd, regulation suspended until closed
Low-pressure alarm delay (IC100CX) — set 30–120 s, AL02 caps trips per hour before manual lockout
Max LP events per hour (IC100CX) — latches unit on overrun, requires manual AL-menu reset
High-pressure alarm delay (IC100CX) — prevents startup nuisance trips, persistent trip indicates condenser fault