EVCO AL11
High discharge pressure pressure regulatorC1 Set OFF all comp. AL21 Low suction
Source: 144RACKNUE05.pdf
What does EVCO AL11 mean?
AL11 on the Evco C-PRO RACK controller signals a high discharge pressure alarm linked to the pressure regulator circuit on circuit 1. When this alarm activates, the controller commands all compressors on circuit 1 to shut down to protect them from operating against excessive head pressure. This is a higher-severity alarm than AL31 (fans-on response) — compressor shutdown is the protective action. The controller must be reset manually after the underlying condition is resolved.
Symptoms
- AL11 displayed on the C-PRO RACK controller.
- All compressors on circuit 1 are shut down.
- High-pressure safety switches on the circuit may also have tripped.
- Discharge pressure is significantly above normal operating range.
- Alarm requires manual reset after the high-pressure condition is cleared.
Common causes
- Severely fouled or blocked condenser coil preventing adequate heat rejection.
- Multiple condenser fans failed simultaneously, leaving no forced airflow across the coil.
- Large refrigerant overcharge — excess liquid refrigerant flooding the condenser and raising head pressure.
- Non-condensable gases (air or nitrogen) introduced during service contaminating the high side.
- High ambient temperature spike combined with reduced condenser performance.
Diagnostic steps
- 01
Do not attempt to restart compressors immediately
AL11 is a protective shutdown. Allow the system to equalize pressure for at least 5 minutes before any restart attempt. Rapid restart against high head pressure damages compressor valves and windings.
- 02
Inspect condenser fans and coil
Confirm all condenser fans are running. Inspect the condenser coil for severe blockage — clean aggressively with coil cleaner and rinse if needed. Check for ice on the coil in low-ambient conditions that could block airflow.
- 03
Check the high-pressure safety switches
Locate the manual-reset high-pressure switches on circuit 1. If tripped, press the reset button only after the cause of high pressure has been addressed. Resetting without fixing the root cause results in repeat compressor shutdown.
- 04
Connect manifold gauges to measure high-side pressure
Attach a manifold gauge set to circuit 1 high-side service ports and read actual discharge pressure. Compare to the saturation pressure at measured ambient temperature to determine whether overcharge or non-condensables are contributing.
- 05
Perform manual reset on the controller and monitor
After corrective action, access the controller alarm menu and perform a manual reset of AL11. Restart the system and observe discharge pressure during the first 15 minutes of operation to confirm the condition does not return.
Keep this fix — get it by email with every EVCO error code
A clean printable version of this EVCO AL11 guide + the full EVCO code pack (26 codes), straight to your inbox. Free.
When to call a professional
AL11 results in compressor shutdown and almost always requires a licensed refrigeration technician to diagnose and resolve. Recovering refrigerant to correct an overcharge, purging non-condensables, diagnosing pressure transducer faults, and evaluating compressor condition after an overpressure event are all tasks requiring EPA Section 608 certification and specialized equipment.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther EVCO error codes
will have no effect the alarm output will be activated CONDENSER Condenser probe
ALdisplayed · No effect on regulation Set the right time. If the error persists, r
AHdisplayed No effect on regulation (A1-A11) Wait until the temperature read by. [
PFis recorded (A4+A11) · If i2 = -1 the alarm is disabled; Check i2 and iP1 [Check
COHdisplayed cSd High condensation|Condenser temperature > Condenser temp. > c6 C7
AL31High discharge pressure C1 Auto ON all fans AL36 High suction pressure C1 Auto O
AL41Low discharge pressure C1 Auto OFF all fans Delay able to be set * AL46 Low suct
AL61Liquid level C1 Manu Visualization Delay able to be set ACC1 Common oil differen
F21Thermal fan 1 Set OFF fan 1 AF22 Thermal fan 2 Set OFF fan 2 AF23 Thermal fan 3
F24Thermal fan 4 Set OFF fan 4 AF01 Hours of operation fan 1 Auto Visualization AF0
F03Hours of operation fan 3 Auto Visualization AF04 Hours of operation fan 4 Auto V
E1X The table below lists the various alarms. Code Meaning Clock error (only if th
Sources: www.evco.it, buildops.com