AskWhiz
E401Lennox

Lennox E401

communicating outdoor unit (Dual fuel module required for heat pump application)

Source: slp99uhv-series__len-slp99uhv-english-iom.pdf

Want this fix in your inbox? Full E401 guide + every Lennox code, printable, free.

What does Lennox E401 mean?

E401 is an informational alert generated by the LSOM (Load Sensing Outdoor Module) on a non-communicating outdoor unit connected to a Lennox communicating furnace control. It fires when the compressor runs more than 18 continuous hours in cooling mode during a single thermostat demand, or when the low-pressure switch trips. The outdoor unit continues to run; no lockout occurs.

Symptoms

  • E401 or 'OD Compressor Long Run Cycle' shown on the thermostat during extended cooling demands.
  • Outdoor unit continues to operate — no shutdown at the point of the alert.
  • On two-stage units with an LED outdoor control, the unit shifts to low speed.
  • Low-pressure switch trips may accompany the alert if refrigerant charge is low.

Common causes

  • Extremely high outdoor ambient temperatures or heat load causing extended compressor run times.
  • Low refrigerant charge reducing system capacity and causing the compressor to run longer to satisfy demand.
  • Undersized equipment for the actual cooling load of the structure.
  • Low-pressure switch trips due to refrigerant leak or evaporator coil icing.

Diagnostic steps

  1. 01

    Check head pressure and suction pressure

    Connect manifold gauges to the service ports and compare operating pressures to the manufacturer's pressure-temperature chart for the refrigerant type. Low suction pressure indicates undercharge or a restriction; high head pressure indicates a condenser or charge issue.

  2. 02

    Inspect condenser coil and fan

    Confirm the condenser fan is running and spinning in the correct direction (drawing air up through the coil). Clean the condenser coil if fins are loaded with debris. A dirty condenser raises head pressure and reduces capacity.

  3. 03

    Check compressor supply voltage

    Measure voltage at the compressor contactor while the compressor is running. Voltage must be within ±10% of nameplate. Low voltage causes extended run times and potential overload.

  4. 04

    Verify low-pressure switch operation

    If low-pressure switch trips are contributing to E401, check refrigerant charge. A system low on charge will trigger the low-pressure switch repeatedly. Do not bypass the low-pressure switch — diagnose the charge or restriction issue.

Keep this fix — get it by email with every Lennox error code

A clean printable version of this Lennox E401 guide + the full Lennox code pack (59 codes), straight to your inbox. Free.

I am a — required, one click

When to call a professional

Refrigerant charging, leak testing, and low-pressure switch diagnosis all require EPA Section 608 certification and refrigerant handling equipment. If the compressor is running more than 18 hours on a properly sized system with correct charge and clean coils, the equipment may be undersized for the load — a Manual J load calculation is required to confirm.

Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.

Open a ticket — free account

Other Lennox error codes

Sources: www.lennox.com, tech.lennoxintl.com