Lennox E401 Error Code
communicating outdoor unit (Dual fuel module required for heat pump application)
Source: slp99uhv-series__len-slp99uhv-english-iom.pdf
What does Lennox E401 mean?
E401 is an informational alert generated by the LSOM (Load Sensing Outdoor Module) on a non-communicating outdoor unit connected to a Lennox communicating furnace control. It fires when the compressor runs more than 18 continuous hours in cooling mode during a single thermostat demand, or when the low-pressure switch trips. The outdoor unit continues to run; no lockout occurs.
Symptoms
- E401 or 'OD Compressor Long Run Cycle' shown on the thermostat during extended cooling demands.
- Outdoor unit continues to operate — no shutdown at the point of the alert.
- On two-stage units with an LED outdoor control, the unit shifts to low speed.
- Low-pressure switch trips may accompany the alert if refrigerant charge is low.
Common causes
- Extremely high outdoor ambient temperatures or heat load causing extended compressor run times.
- Low refrigerant charge reducing system capacity and causing the compressor to run longer to satisfy demand.
- Undersized equipment for the actual cooling load of the structure.
- Low-pressure switch trips due to refrigerant leak or evaporator coil icing.
Ask the AskWhiz AI about Lennox E401
AskWhiz
online
Diagnostic steps
Check head pressure and suction pressure
Connect manifold gauges to the service ports and compare operating pressures to the manufacturer's pressure-temperature chart for the refrigerant type. Low suction pressure indicates undercharge or a restriction; high head pressure indicates a condenser or charge issue.
Inspect condenser coil and fan
Confirm the condenser fan is running and spinning in the correct direction (drawing air up through the coil). Clean the condenser coil if fins are loaded with debris. A dirty condenser raises head pressure and reduces capacity.
Check compressor supply voltage
Measure voltage at the compressor contactor while the compressor is running. Voltage must be within ±10% of nameplate. Low voltage causes extended run times and potential overload.
Verify low-pressure switch operation
If low-pressure switch trips are contributing to E401, check refrigerant charge. A system low on charge will trigger the low-pressure switch repeatedly. Do not bypass the low-pressure switch — diagnose the charge or restriction issue.
When to call a professional
Refrigerant charging, leak testing, and low-pressure switch diagnosis all require EPA Section 608 certification and refrigerant handling equipment. If the compressor is running more than 18 hours on a properly sized system with correct charge and clean coils, the equipment may be undersized for the load — a Manual J load calculation is required to confirm.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Lennox documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Lennox Error Codes
Diagnostic Codes/Status of Equipment Soft lockout - Exceeded maximum number of A
. recycles. Last recycle failed due to the limit circuit opening or limit remain
E276 E290 E291 E292 Soft lockout - Flame sensed out of sequence from code 241 fa
Combustion air inducer motor amp draw is too Check combustion blower bearings, w
Indoor blower motor temperature is too high. Indoor blower motor over temperatur
Discharge error sensor failure - No error if Discharge air temperature(DATS) out
Heat rate reduced to match indoor blower air Furnace blower in cutback mode due
Restricted air flow in cooling or continuous fan Restricted airflow - Indoor blo
Indoor or outdoor unit capacity mismatch. Incorrect Indoor /outdoor capacity cod
E347 E348 E349 Global network connection - Communication link problem. No 24 Vol
LSOM - Outdoor unit system pressure trip. Compressor ran over 18 hours in air co
LSOM - Compressor short-cycling (Running less than 4 minutes). Outdoor unit pres
Sources: www.lennox.com, tech.lennoxintl.com