Reznor 1 Flash Error Code
Combustion pressure switch open with blower on
Source: hvac/reznor/f1bb6ebc__vcs-60__rez-vcs-vct-iom-2806-21-29-270685-a-english-iom.pdf
What does Reznor 1 Flash mean?
On Reznor radiant tube heaters with the UT burner controller, a single flash of the diagnostic LED means the combustion air pressure switch is reading open while the blower is running. The control expects the switch to close once the blower proves combustion airflow, so an open switch during blower operation blocks the ignition sequence and prevents the burner from firing.
Symptoms
- Diagnostic LED on the burner controller flashes once, repeatedly
- Blower runs but the main burner never ignites
- No heat output from the radiant tube heater
- Unit cycles on a call for heat without establishing flame
Common causes
- Combustion air pressure switch stuck or failed open
- Blocked, disconnected, or cracked pressure switch sensing tube
- Obstructed flue, vent terminal, or combustion air inlet
- Weak or failing combustion blower not generating enough pressure
- Loose or damaged wiring between the pressure switch and controller
Ask the AskWhiz AI about Reznor 1 Flash
AskWhiz
online
Diagnostic steps
Confirm the flash count
Observe the controller LED and verify it is a single repeating flash, distinguishing it from the steady-on (control OK) and other multi-flash fault states.
Inspect the sensing tube
Check the silicone tube to the combustion pressure switch for kinks, cracks, blockage, or disconnection and reseat it securely.
Verify the blower and air path
Confirm the combustion blower runs on a call for heat and check that the flue, vent terminal, and combustion air inlet are clear of obstruction.
Check the pressure switch and wiring
Inspect the pressure switch wiring connections for damage; the IOM directs replacing the air pressure switch when it does not respond correctly.
When to call a professional
Diagnosing and replacing the combustion pressure switch, blower, or controller involves live gas and electrical components, and the manual requires turning off the gas and all electrical supplies before any repair work. If the LED still flashes once after checking the sensing tube and air path, have a qualified gas heating technician verify switch operation, blower performance, and the venting system before returning the heater to service.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Reznor documentation and can diagnose this fault code and guide you through the repair in minutes.
5 free questions per bot in your browser — no signup.
Other Reznor Error Codes
AskWhiz Playground
Test your diagnostic skills
Play a real HVAC service call in the AskWhiz Playground — real brands, real fault codes, no signup.
Play a real service call