Weil McLain F40 Error Code
repeated 3 times in the last hour A41 Temperature sensor not or bad connected to
Source: ab-80c__wml-aquabalance-series-2-iom.pdf
What does Weil McLain F40 mean?
F40 indicates the central heating system water pressure has exceeded the high-pressure limit as detected by the water pressure sensor. When the pressure trips the high threshold (confirmed over 2 seconds), the controller disables heat demand and shuts off the pumps to protect the system. The fault also fires when a control fault is detected.
Symptoms
- Boiler displays F40 and stops heating.
- System pressure gauge reads above normal operating range.
- Boiler and circulator pumps shut off simultaneously.
- Fault recurs shortly after reset if the pressure source is not corrected.
Common causes
- Pressure reducing valve (fill valve) stuck open, continuously adding water to the system.
- Expansion tank waterlogged or undersized, causing pressure to spike during heating.
- Relief valve not releasing pressure as expected, allowing buildup.
- Water pressure sensor wiring fault triggering a false high-pressure reading.
- Control board fault triggering the F40 code without an actual pressure event.
Ask the AskWhiz AI about Weil McLain F40
AskWhiz
online
Diagnostic steps
Read the system pressure gauge
Check the boiler pressure/temperature gauge. If pressure is above 30 psi, the high-pressure condition is real. If gauge reads normal, suspect a sensor or control fault.
Inspect the fill valve
Close the fill valve and monitor pressure. If pressure continues rising, the valve is passing water and must be repaired or replaced.
Check the expansion tank
Isolate and drain the expansion tank, then measure the pre-charge pressure. A waterlogged tank (zero air charge) must be replaced to restore proper pressure absorption.
Inspect water pressure sensor wiring
Check the sensor connector for corrosion, loose pins, or shorting. A shorted pressure sensor can produce a false F40 without any actual over-pressure condition.
Reset and monitor
After correcting the pressure source, press Reset for 1.5 seconds. Watch the pressure gauge during the next heating cycle to confirm pressure stays within the normal operating range.
When to call a professional
Call a technician if the pressure source cannot be identified, the expansion tank replacement does not resolve the issue, or if F40 is associated with a control fault rather than actual over-pressure. Diagnosis requires system pressure analysis and potentially water pressure sensor replacement.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Weil McLain documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Weil McLain Error Codes
prom parameters Unit Range Def Description Num. Address Description Low High Val
Firmwareversion Num 0 99 04
repeated 3 times in the last 24 hours LP Liquefied Petroleum (Propane) Gas LWCO
generated for 1 hour (con- secutive) See fault F15 A06 No flame after igni- tion
Supply sensor 1 fault Sensor damaged Wiring shorted Check the wiring or replace
Return sensor fault Sensor damaged Wiring shorted Check the wiring or replace th
DHW sensor fault Sensor damaged Wiring shorted Check the wiring or replace the s
flashing (history/fault) ·Push “Reset" once · Push + to scroll error codes, refe
4C - selection). F34 Low mains voltage. F35 Frequency error. F37 The water press
The Exhaust gases temperature sensor error. F14 The CH supply water temperature
The water pressure in the CH installation is near the high level. F27 The exhaus
Low mains voltage. F35 Frequency error. F37 The water pressure in the CH install
Sources: freeboilermanuals.com