Danfoss E15
Cut-out S2 sensor
Source: Danfoss 10/BC164086425207en-000401.pdf
What does Danfoss E15 mean?
E15 indicates a cut-out (open-circuit) on the S2 sensor of a Danfoss EKC controller. The S2 input has lost its signal, so the controller can no longer read that temperature. Because S2 is a regulating sensor, regulation may switch to a safety delay mode (status S44) while the fault is present. The alarm relay activates at high priority.
Symptoms
- Display shows E15 when the alarm is recalled.
- Controller reports the S2 reading as missing or out of range.
- Front-panel LEDs flash to indicate the regulation error.
- Controller may enter the S44 safety-delay state while a regulating sensor has failed.
Common causes
- S2 sensor cable is broken or open-circuit.
- Loose or corroded terminal at the S2 connection.
- Failed S2 temperature sensor.
- Sensor reading driven outside its valid measuring range.
Diagnostic steps
- 01
Recall and acknowledge the alarm
Press the top button to display the E15 code, then press again to cancel the active alarm so you can investigate.
- 02
Inspect the S2 wiring
Power down, then check the S2 sensor cable and terminals for breaks, looseness, or corrosion. Re-seat the connection.
- 03
Measure the S2 sensor
Disconnect S2 and measure its resistance with a multimeter; an open-circuit reading confirms a failed sensor or broken cable.
- 04
Replace the S2 sensor
Fit a new sensor of the type specified for the controller, route the cable away from power wiring, and confirm E15 clears on power-up.
Keep this fix — get it by email with every Danfoss error code
A clean printable version of this Danfoss E15 guide + the full Danfoss code pack (26 codes), straight to your inbox. Free.
When to call a professional
Clearing E15 means locating a broken sensor circuit on a live refrigeration control. If you cannot find the open circuit, or the sensor is in a difficult location, call a refrigeration technician. They can verify the correct sensor type, confirm the controller is reading S2 again, and restore safe superheat or temperature regulation. Working inside the control panel carries an electrical-safety risk for untrained staff.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Danfoss error codes
Fault in controller
E16Short circuited S2 sensor
E17Cut-out S3 sensor
E18Short circuited S3 sensor
E20Fault on signal from Pc (condensing pressure transmitter)
E39Fault on signal from P0 (evaporating pressure transmitter)
A11No refrigerant has been selected
A43Step motor fault (valve output or phase)
A45Regulation stopped — main switch off (standby mode)
E29Sair sensor error — air temperature sensor
E27Def sensor error — S5 evaporator sensor
E30Sc sensor error — condenser sensor