Danfoss E30
Sc sensor error — condenser sensor
Source: Danfoss 10/BC194286421698en-001101.pdf
What does Danfoss E30 mean?
On the Danfoss ERC 21X controller, E30 means the Sc (condenser) sensor is defective or its electrical connection is lost. The controller monitors condenser temperature to protect the compressor and trigger condenser alarms, so losing this sensor removes that protection. The display alternates between the air temperature and the active alarm codes, and the alarm relay is activated.
Symptoms
- Display alternates between air temperature and the code E30.
- Condenser temperature reading is missing or faulted.
- Condenser high-temperature protection (A61/A80) cannot operate.
- Alarm relay is activated.
Common causes
- Condenser (Sc) sensor is defective.
- Electrical connection to the condenser sensor is lost or broken.
- Sensor cable damaged near the hot condenser section.
- Loose or corroded terminal at the sensor input.
Diagnostic steps
- 01
Confirm the alarm source
Read the display alternating between air temperature and E30 to identify the condenser sensor as the fault.
- 02
Inspect the condenser sensor wiring
Power down and check the Sc cable and terminals, allowing for heat damage near the condenser.
- 03
Measure the sensor
Disconnect Sc and measure its resistance against the fitted sensor type; an open or shorted reading confirms a failed sensor.
- 04
Replace the condenser sensor
Fit a new sensor of the correct type, mount it as before on the condenser, and confirm E30 clears on power-up.
Keep this fix — get it by email with every Danfoss error code
A clean printable version of this Danfoss E30 guide + the full Danfoss code pack (26 codes), straight to your inbox. Free.
When to call a professional
Without the condenser sensor the controller cannot warn of a blocked or overheating condenser, which risks compressor damage. If E30 persists after replacement, a refrigeration technician should verify the sensor type, mounting, and the condenser-alarm settings. Trained diagnosis ensures condenser protection is restored and that any underlying overheating cause, such as restricted airflow, is also addressed.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Danfoss error codes
Fault in controller
E15Cut-out S2 sensor
E16Short circuited S2 sensor
E17Cut-out S3 sensor
E18Short circuited S3 sensor
E20Fault on signal from Pc (condensing pressure transmitter)
E39Fault on signal from P0 (evaporating pressure transmitter)
A11No refrigerant has been selected
A43Step motor fault (valve output or phase)
A45Regulation stopped — main switch off (standby mode)
E29Sair sensor error — air temperature sensor
E27Def sensor error — S5 evaporator sensor
AskWhiz Playground
Test your diagnostic skills
Play a real HVAC service call in the AskWhiz Playground — real brands, real fault codes, no signup.
Play a real service call