Delfield error codes, decoded.

Look up any Delfield fault code below. Each one is grounded in Delfield's own service documentation — the meaning, the symptoms, the causes, and the steps to clear it.

Quick answer

Delfield (Welbilt / Ali Group) builds US commercial refrigeration — prep tables, undercounter freezers, Specification-Line walk-ins, and T5 blast chillers. Most fault codes come from the underlying Dixell or Carel controller: P1 / P2 / E1 / E2 cabinet- and evaporator-probe NTC faults, HA / LA high- and low-temperature alarms, EE EEPROM, dEF for active defrost.

NH

By Nichita Herput

Co-founder & CEO · Reviewed May 2026

Working on a Delfield unit? The complete Delfield code pack in your inbox — free.

Delfield sits in our Commercial Kitchen coverage. Every page here is transcribed from the manufacturer's manuals, not scraped from forums.

What error codes does Delfield display?

Tap a code for the full breakdown — meaning, symptoms, causes, and fix steps.

P1

Cabinet probe Pb1 NTC fault on Dixell-based Delfield controllers — controller falls back to Ont / OFt duty-cycle, cabinet not regulated to setpoint; ohm probe (10 kΩ at 25 °C), replace if open / shorted.

P2

Evaporator / defrost-termination probe Pb2 NTC fault — defrost cycle ends on MdF time-out only; replace probe to restore temperature-terminated defrost on reach-ins, prep tables, and walk-ins.

E1

Cabinet probe fault on newer Dixell firmware and on Carel ir33 / Easy controllers — same diagnostic path as P1; controller suspends regulation.

E2

Evaporator probe fault on newer firmware — same diagnostic as P2; defrost end disabled.

HA

High-temperature alarm referenced to Pb1 — cabinet above AH threshold for longer than Ad delay; check dirty condenser, door gasket, condenser fan, refrigerant charge.

LA

Low-temperature alarm — cabinet below AL threshold; check stuck hot-gas valve, extended defrost overrun, probe positioned on evaporator coil.

EA

External alarm — digital input EAL closed; check field-wired safety device (compressor protection, phase loss, panel safety) and i1P input-polarity parameter.

dA

Door alarm — door-switch input held active beyond the OAd door-open delay; regulation suspended until door closes.

dEF

Defrost cycle currently active — normal during programmed defrost window; force-end with snowflake button if stuck past MdF.

EE

EEPROM checksum / non-volatile-memory fault on the controller — board replacement typically required, parameter set must be reloaded from a commissioning sheet or the Delfield service manual.