Utica Dunkirk error codes, decoded.
Look up any Utica Dunkirk fault code below. Each one is grounded in Utica Dunkirk's own service documentation — the meaning, the symptoms, the causes, and the steps to clear it.
Quick answer
Utica Boilers and Dunkirk are sister US boiler brands under ECR International, sharing gas and oil platforms — DCC/DCB and DCCF/DCBF condensing, DMG-240 modulating, SSE/UB/UCS/USVA cast-iron, UB90 condensing, and Megasteam oil. Modern controls show 2–3 digit E-prefix fault codes covering ignition, sensor, pressure, blower, and combustion-calibration faults — most common are E110, E130, E36, E42, E55, and E72.
Co-founder & CTO · Reviewed May 2026
Utica Dunkirk sits in our HVAC coverage. Every page here is transcribed from the manufacturer's manuals, not scraped from forums.
What error codes does Utica Dunkirk display?
Tap a code for the full breakdown — meaning, symptoms, causes, and fix steps.
Supply temperature sensor open circuit — reseat connector or replace NTC
E08Return temperature too low — check return NTC, circulation, supply/return reversal
E12Heat exchanger high-limit overheat — verify circulation, P35 setpoint
E36Flame loss during operation — gas pressure, electrode, flue draw
E38SCU PCB communication error — check D3 LED, run auto-detect after removal
E42Onboard low water pressure switch open — refill, check for leaks
E44Supply/return Delta-T too high — pump flow, zone valves, sensor swap, P35
E55PCB unprogrammed/uncalibrated — run automatic + manual calibration
E65Fan reached max speed correcting flame signal — flue recirculation or fouled electrode
E72Combustion test alarm during auto-calibration — gas pressure, recirculation, electrode, P02
Get the complete Utica Dunkirk error-code pack by email
Every Utica Dunkirk code, meaning and first checks in one document you can save, print or forward. Free.
Common questions about Utica Dunkirk equipment
Other HVAC brands we cover