York 2 Flashes
Induced draft pressure switch did not close — the switch failed to prove airflow within 10 seconds of the inducer starting.
Source: York 3/York_INSTALLATION-MANUAL-ZX-A7-08-TO-14-SER_InstallationGuide_HVAC_EN-5513316-uim-c-0819.pdf
What does York 2 Flashes mean?
Two flashes means the induced draft pressure switch did not close: 24 VAC was not received at the control's pressure-switch input (P1-8) within 10 seconds of the ignition control energizing the inducer, or 24 VAC was later lost while the inducer was running. Gas valve operation is not permitted. The output relay cycles closed for five minutes then open for 30 seconds, retrying until the switch proves closed or the heating demand ends.
Symptoms
- Burners do not light; no heat is produced
- Inducer motor runs but the furnace never advances to ignition
- ICB flashes a counted burst of 2 on the LED
- Unit retries in a repeating five-minute-on, 30-second-off pattern
Common causes
- Induced draft motor is not running or is weak
- Blockage in the combustion air or induced draft path
- Cracked, disconnected, or pinched pressure-switch sensing tubing
- Pressure switch out of calibration or failed open
- Open L1-to-IND contacts in the inducer circuit
Diagnostic steps
- 01
Confirm the inducer is operating
Verify the induced draft motor runs and the blower wheel is intact, and check that the L1 to IND contacts are not open.
- 02
Clear the combustion air path
Inspect the induced draft and combustion air passages for blockages and remove any obstructions.
- 03
Inspect the sensing tubing
Verify the pressure-switch sensing tubing is intact and free of cracks, kinks, or disconnections.
- 04
Verify the switch setpoint
Tee an inclined or digital manometer into the sensing line and confirm the negative pressure exceeds the value on the switch label so the contacts close at the rated setting.
- 05
Confirm switch closure
Check that the pressure switch contacts close correctly at the labeled setting; replace the switch if it will not close under proven draft.
Keep this fix — get it by email with every York error code
A clean printable version of this York 2 Flashes guide + the full York code pack (12 codes), straight to your inbox. Free.
When to call a professional
Verifying pressure-switch setpoints requires a manometer or Magnehelic gauge and the ability to interpret negative-pressure readings against the switch label. If the inducer runs and the venting is clear but the switch still will not prove, call a licensed HVAC technician to measure draft and confirm the switch and wiring. A persistent draft-proving failure can also signal a vent or heat-exchanger problem that needs professional combustion diagnosis.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther York error codes
Normal operation — the ignition control board is powered and ready to respond to a heating demand.
Steady OffLED is steady off — no power to the control, or the control has suffered catastrophic damage.
Steady OnLED is steady on — the control's microprocessor has not passed its self-check.
3 FlashesInduced draft pressure switch stuck closed — the switch reads closed at the same moment a call for heat begins.
4 FlashesFlame could not be established — no flame was sensed in three consecutive ignition attempts (lockout).
5 FlashesFlame loss — an established flame dropped out five times during one heating cycle (lockout).
6 FlashesOpen limit — 24 VAC was lost at the limit-switch input for six minutes or less during a call for heat.
7 FlashesOpen rollout — 24 VAC was lost at the control's flame rollout switch input.
8 FlashesGas valve failed to shut off — flame was sensed for more than 2 seconds after the gas valve output was turned off.
9 FlashesIndoor airflow failure / open limit — limit input lost 24 VAC for more than six minutes during a call for heat (hard lockout).
10 FlashesGas valve miswire or gas valve relay fault — unexpected or missing 24 VAC at the gas valve outputs.