ACiQ PC00
Outdoor IPM module protection
Source: ACiQ/ACiQ_ACIQ-SZ-ODU-EH-SH-SM-EN-01-051625-6K-60K-230V-NA-H-240527_ServiceManual_HVAC_EN.pdf
What does ACiQ PC00 mean?
PC00 is an outdoor IPM (Intelligent Power Module) protection fault. The IPM drives the inverter compressor, and its protection trips when the module detects an abnormal condition. The diagnosis centers on the IPM board, the signal wiring between the IPM and main board, and the outdoor main control board.
Symptoms
- PC00 shown on the display
- Compressor will not run or stops shortly after starting
- Outdoor unit protection trips repeatedly
- No or weak heating and cooling output
Common causes
- Faulty IPM module board
- Loose or broken signal wire between the IPM board and main board
- Faulty outdoor main control board
- Fault in the electric control box
Diagnostic steps
- 01
Check the IPM board LED
Verify at least one LED on the IPM board is lit, indicating the board is powered.
- 02
Inspect the signal wiring
Check the signal wire between the IPM board and the main board and confirm it is connected properly; reconnect and retry.
- 03
Replace the IPM board
If the fault persists with good wiring, replace the IPM board and check whether the system runs normally.
- 04
Replace the outdoor main board
If the fault remains, replace the outdoor main board.
- 05
Replace the electric control box
If the problem still is not resolved, replace the electric control box.
Keep this fix — get it by email with every ACiQ error code
A clean printable version of this ACiQ PC00 guide + the full ACiQ code pack (20 codes), straight to your inbox. Free.
When to call a professional
PC00 involves the high-voltage inverter power module, where capacitors store dangerous charge even after the power is off and must be fully discharged before any work. Diagnosis requires antistatic precautions and board-level replacement. Always contact a licensed HVAC technician for PC00; the IPM, main board, and control-box work on these inverter condensers is hazardous and must be done by a qualified professional.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther ACiQ error codes
Indoor and outdoor unit communication error
EL0CSystem lacks refrigerant
EH00Indoor unit EEPROM malfunction / parameter error
EH02Zero-crossing signal detection error
EH03Indoor unit fan speed out of control
EH60Indoor unit room temperature sensor (T1) error
EH61Indoor unit pipe temperature sensor (T2) error
EC51Outdoor unit EEPROM parameter error
EC52Outdoor unit coil temperature sensor (T3) error
EC53Outdoor unit ambient temperature sensor (T4) error
EC54Compressor discharge temperature sensor (TP) error
EC07Outdoor unit fan speed out of control
AskWhiz Playground
Test your diagnostic skills
Play a real HVAC service call in the AskWhiz Playground — real brands, real fault codes, no signup.
Play a real service call