Ako E11 Error Code
E2 Probe 1 or 2 faulty (open circuit, crossover or temperature outside the probe
Source: 351763502-2.pdf
What does Ako E11 mean?
On AKO advanced cold room controllers (AKO-16524A/16525A/16526 series), E11 indicates that probes S1 and S2 are reading similar temperatures — meaning there is insufficient temperature difference between the cold room and evaporator probes. This prevents the SELFDRIVE self-calibration system from operating correctly and indicates either a probe positioning problem or a refrigeration issue.
Symptoms
- E11 appears on the display.
- SELFDRIVE calibration cannot complete or has been suspended.
- Controller falls back to standard (non-optimized) regulation mode.
- Alarm relay activates.
- Cold room and evaporator temperatures are unusually close together.
Common causes
- Probe S2 (evaporator probe) is incorrectly positioned and reading air temperature close to S1 (most common).
- Refrigeration system fault causing the evaporator to warm up to cold-room temperature.
- Probes S1 and S2 have been swapped during installation or replacement.
- Refrigerant shortage causing poor evaporator performance and a warm evaporator.
- Blocked airflow over the evaporator reducing the temperature differential.
Ask the AskWhiz AI about Ako E11
AskWhiz
online
Diagnostic steps
Verify probe S2 position on the evaporator
Confirm S2 is properly clipped to the evaporator coil — not hanging in free air or positioned on the return air side. The evaporator probe must sense the coldest point of the coil to provide adequate differential.
Confirm S1 and S2 are not swapped
Trace the probe cables to their terminals. S1 goes to the cold-room air and S2 to the evaporator coil. Swapped probes produce identical-looking readings and trigger E11.
Check evaporator for ice blockage
Inspect the evaporator for heavy frost or ice that may be insulating the probe from the coil. If heavily iced, initiate a manual defrost cycle and recheck the temperature differential.
Monitor refrigeration system performance
After correcting probe positions and clearing ice, observe whether the temperature difference between S1 and S2 increases to a normal range (typically more than a few degrees). Persistent similarity suggests a refrigerant issue.
Restart SELFDRIVE calibration after resolving the cause
Once the temperature differential is restored, the controller can re-enter SELFDRIVE calibration mode. Consult the AKO-16524A manual for the SELFDRIVE restart procedure.
When to call a professional
Call a licensed refrigeration technician if E11 persists after correcting probe positions and clearing ice, as the flat evaporator–cold room temperature differential is a classic sign of low refrigerant charge or a failing expansion valve. Refrigerant system diagnosis and repair require certified handling of refrigerants.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Ako documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Ako Error Codes
/E3 Probe 1/2/3 failure (Open circuit, crossed circuit or temperature outside th
Severe external alarm activated (by digital input) Rdt Defrost alarm concluded d
/ E2/ E3 Probe 1, 2 or, 3 faulty. Severe external alarm activated. AES Indicates
configuration. It allows the creation of up to 5 user profiles, each with a four
Indicates a defrost is underway. After defrosting, the message wilcontinue to be
Access code (Password)request Probe1brokenOpen,rosdcicuit or proeutofrane Memory
Thermal alarm 3 DR RE4 Thermal alarm 4 DR RE5 Thermal alarm 5 DR RE5 Severe exte
E3 Probe 1, 2 or 3 faulty (open circuit, crossover or temperature outside the pr
) (Does not activate alarm relay) (See page 16)
Severe external alarm activated due to digital input 15 or 16 (According to para
Regulation remotely stopped due to digital input 15 or I6; all stages/compressor
and AL6. These values comply with domestic and international regulations RSIF, E
Sources: help.ako.com, help.ako.com