Carel E7
Prob DeS2Hfaultyordisconnected NO [NO INO Automatic Ed1 Defrost terminated NO NO
Source: 0300100EN.pdf
What does Carel E7 mean?
On Carel refrigeration controllers (source document 0300100EN.pdf), the E7 alarm indicates that probe DeS2H (the defrost S2 probe) is faulty or disconnected. This probe measures the evaporator temperature used to terminate defrost cycles by temperature. When E7 is active, defrost termination by temperature is unavailable and the controller may fall back to a time-limited defrost or disable defrost depending on configuration.
Symptoms
- E7 displayed on the controller alternating with temperature.
- Defrost termination by temperature is unavailable; cycle runs to time limit.
- Alarm relay activates.
- Evaporator temperature monitoring for defrost control is lost.
Common causes
- DeS2H probe wiring open-circuit or disconnected at the probe or controller terminal.
- NTC sensor element failed — open or short circuit.
- Probe cable damaged by ice formation or mechanical contact during defrost cycle.
- Corrosion on the probe connector terminal from repeated freeze-defrost cycling.
Diagnostic steps
- 01
Locate and inspect the DeS2H probe
Find the defrost S2 probe clipped to the evaporator coil. Check for ice encasement, physical damage, or loose mounting.
- 02
Measure probe resistance
Disconnect the probe from the controller and measure resistance across the two leads. A healthy NTC at 0 °C reads approximately 6 kΩ; open or short confirms failure.
- 03
Inspect the cable to the controller
Trace the cable from the evaporator to the controller terminal. Look for cuts, pinch damage from ice, or corroded terminals.
- 04
Replace the defrost probe
Install a compatible Carel NTC probe in the same evaporator location. Secure it with a probe clip so it has firm thermal contact with the coil.
- 05
Reset and confirm defrost operation
Clear the E7 alarm, trigger a manual defrost cycle, and verify the controller terminates defrost based on the probe reaching the configured end-defrost temperature.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel E7 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
Escalate to a refrigeration technician if E7 persists after probe replacement, or if repeated probe failures occur — indicating the evaporator environment is damaging probes faster than normal due to ice bridging or aggressive defrost temperatures. A technician should also verify defrost cycle configuration to ensure it does not risk compressor liquid slugging when probe-based termination is unavailable.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, becoolrefrigeration.co.uk