Coreco IA
Immediate or delayed alarm from the multifunction digital input (external alarm)
Source: Coreco_easy_compact_eng_termostatos.pdf
What does Coreco IA mean?
On the Coreco controller (Carel easy / easy compact), IA is the external alarm raised through the multifunction digital input when it is set as an alarm input (parameter A4=1). The signal can be immediate or delayed by parameter A7. When detected, the controller flashes IA, sounds the buzzer and stops the compressor due to external alarm while the fan keeps running per its parameters. The alarm resets automatically.
Symptoms
- Display shows IA flashing alternating with the temperature
- Buzzer sounds when the alarm is enabled
- Compressor stops due to the external alarm (immediate when A7=0)
- Evaporator fan continues to run according to its parameters
- Any defrost or continuous cycle in progress is interrupted
Common causes
- External device wired to the digital input has signalled an alarm
- Digital input contact opened with A4=1 (open = alarm detected)
- Fault or trip in the connected external protection device
- Incorrect A4 / A7 multifunction-input configuration
- Wiring problem on the multifunction digital input
Diagnostic steps
- 01
Recognise the external-alarm source
IA is an immediate or delayed alarm from the multifunction digital input. Check the external device wired to that input to see what condition it has flagged.
- 02
Mute the buzzer
Press SET to silence the buzzer; the IA code clears once the external alarm condition ends.
- 03
Check the multifunction input and parameters
Verify the multifunction input wiring and parameters A4 and A7 — A4=1 sets the input as an external alarm and A7 sets the detection delay.
- 04
Investigate the connected device
Inspect whatever protection or device drives the input contact, since with A4=1 an open contact is read as an alarm and a closed contact as normal operation.
- 05
Confirm recovery
When the external alarm ceases the unit resumes normal operation — a continuous cycle can run, defrosts can run, and the compressor restarts after its minimum off time (parameter c2).
Keep this fix — get it by email with every Coreco error code
A clean printable version of this Coreco IA guide + the full Coreco code pack (49 codes), straight to your inbox. Free.
When to call a professional
Because IA originates from an external device wired into the controller, have a qualified technician trace the source if it is not obvious or recurs. Access to the cabinet's electrical parts is reserved for qualified personnel, who can verify the A4/A7 settings, the input wiring and the connected protection device so the external alarm is correctly diagnosed and cleared.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Coreco error codes
Control probe (probe 1) error — signal interrupted, short-circuited or incompatible probe
E1Evaporator / defrost probe (probe 2) error — signal interrupted, short-circuited or incompatible probe
E2Condenser / product probe (probe 3) error — signal interrupted, short-circuited or incompatible probe
dOrOpen-door alarm from the door-switch digital input
LOLow-temperature alarm — measured temperature below set point by more than parameter AL
HIHigh-temperature alarm — measured temperature above set point by more than parameter AH
EEUnit parameter reading (data) error — saved configuration data error
EFOperating parameter reading (data) error — manual reset
EdDefrost ended by timeout — last defrost stopped on maximum duration, not on temperature
dFDefrost running — status message shown during a defrost cycle (not an alarm)
CHtDirty-condenser warning/alarm — pre-alarm (cht) between Ac-AE and Ac, then alarm (CHt) when Ac is exceeded and refrigeration stops (manual reset)
EtCInternal clock (RTC) alarm — clock fault; reset by setting the time