Eliwell HA1
Meaning HIGH temperature alarm, refers to probe LA1 LOW temperature alarm, refer
Source: EWRCNTAIR_User-Manual_EN_id1300.pdf
What does Eliwell HA1 mean?
HA1 is the high temperature alarm on probe Pb1 in Eliwell controllers. It activates when the cabinet or room temperature measured by Pb1 rises above the configured high-limit threshold (HAL parameter). The alarm is logged and the relay may activate, but refrigeration regulation continues — the controller does not block the compressor in response to HA1.
Symptoms
- Display alternates between 'HA1' and the current measured temperature.
- Alarm event is recorded in the controller's alarm log (AL folder).
- Alarm relay activates if configured.
- Buzzer sounds if fitted and enabled.
- Normal refrigeration regulation continues without interruption.
Common causes
- Cabinet temperature has risen above the configured high-limit alarm threshold (HAL parameter).
- Refrigeration system performance reduced due to dirty condenser coils or low refrigerant charge.
- Door left open or door seal defective, allowing warm air infiltration.
- High ambient temperature exceeding unit design limits.
- HAL parameter set too close to operating setpoint, causing nuisance alarms.
Diagnostic steps
- 01
Verify the actual cabinet temperature
Compare the controller reading with an independent calibrated thermometer to confirm the temperature is genuinely elevated.
- 02
Check the HAL alarm threshold parameter
Enter the programming menu and confirm HAL (or HA1) is set to an appropriate value for the application. Adjust if it is set too close to the operating setpoint.
- 03
Inspect condenser coils and airflow
Clean the condenser coils of dust and debris. Verify that airflow across the condenser is unobstructed and that the condenser fan is running at the correct speed.
- 04
Check door seals and closing mechanism
Inspect door gaskets for damage or gaps. Confirm the door closes fully and the latch engages properly to prevent warm-air infiltration.
- 05
Monitor recovery and clear the alarm
After addressing the root cause, press any key to acknowledge the alarm. Observe the temperature trend to confirm the cabinet is recovering toward setpoint.
Keep this fix — get it by email with every Eliwell error code
A clean printable version of this Eliwell HA1 guide + the full Eliwell code pack (18 codes), straight to your inbox. Free.
When to call a professional
If the cabinet temperature does not recover toward setpoint after cleaning the condenser and verifying door seals, a licensed refrigeration engineer should check refrigerant charge, measure subcooling and superheat, and test compressor efficiency. Sustained high temperatures in food-storage applications are a HACCP critical control point requiring documented corrective action.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Eliwell error codes
Pb1 probe error active Automatic Ont, OFt E2 Pb2 probe error active Automatic On
E3Pb3 probe error active Automatic Ont, OFt HA1 HIGH temperature alarm active Auto
E2, dAt PAn Panic alarm not active Automatic ALd leak detector alarm not active Au
E10Clock alarm not active Automatic PA General pressure switch alarm not active Man
LA1in folder AL · Relay on (if configured) · No effect on regulation · Record label
F1and QF2) · Motor overload protection terminals (QM1) Cleaning Do not use abrasiv
E4displayed · check probe type (H00) operating range · check the probe wiring? · p
E5displayed · check probe type (H00) · check the probe wiring E6 Pb6 probe error (
E6displayed · alarm icon permanently on · check the probe type · check the probe w
E7· measured values are outside operating range · label E7 displayed · alarm icon
AL1AH2 set in tA1. Value read by probe 1 · no effect on regulation · no effect on r
AL2Value read by probe 2 · recording of label AL2 in folder ALr · no effect on regu
Sources: becoolrefrigeration.co.uk, www.eliwell.com