Eliwell LA1
in folder AL · Relay on (if configured) · No effect on regulation · Record label
Source: EWRC5000-AIR_User-Manual_EN_id1212.pdf
What does Eliwell LA1 mean?
LA1 is the low temperature alarm on probe 1 (Pb1). The controller triggers this alarm when the measured cabinet temperature drops below the configured minimum threshold (parameter LAL or LA1 limit). The alarm is logged in the alarm folder and does not block refrigeration regulation — compressor control continues normally.
Symptoms
- Display alternates between 'LA1' and the current temperature reading.
- Alarm is recorded in the controller's alarm log (AL folder).
- Alarm relay activates if configured.
- Buzzer sounds if fitted and enabled.
- Normal refrigeration regulation continues without interruption.
Common causes
- Cabinet temperature has dropped below the configured low-limit alarm threshold (LAL parameter).
- Low alarm threshold is set too close to the operating setpoint, causing nuisance trips.
- Refrigeration system is over-cooling due to a stuck-open expansion valve or thermostat fault.
- Door left open in cold weather allowing ambient temperatures below the alarm limit.
- Pb1 probe reading is inaccurate due to ice formation or poor placement.
Diagnostic steps
- 01
Check the actual cabinet temperature
Read the temperature displayed on the controller and compare it with an independent thermometer inside the cabinet to confirm the reading is accurate.
- 02
Review the low alarm limit parameter (LAL)
Enter the programming menu and check the LAL (or LA1) parameter. If it is set too close to the operating setpoint, adjust it to a value appropriate for the application.
- 03
Inspect the Pb1 probe location and condition
Confirm the probe is positioned correctly in the air stream, is not covered by ice, and is not adjacent to the evaporator coil where it could read abnormally low values.
- 04
Investigate refrigeration system for over-cooling
Check whether the compressor or expansion valve is causing excessive refrigerating effect. Verify setpoint, differential, and compressor run-time parameters are appropriate.
- 05
Reset and monitor the alarm
Press any button to silence the buzzer and clear the alarm LED. Monitor temperature over the next full cycle to confirm it stays within limits.
Keep this fix — get it by email with every Eliwell error code
A clean printable version of this Eliwell LA1 guide + the full Eliwell code pack (18 codes), straight to your inbox. Free.
When to call a professional
If the cabinet temperature is genuinely below the safe storage limit and adjusting alarm parameters does not resolve the root cause, or if the refrigeration system appears to be running continuously without controlling temperature, a certified refrigeration engineer should inspect the expansion valve, refrigerant charge, and thermostat calibration.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Eliwell error codes
Pb1 probe error active Automatic Ont, OFt E2 Pb2 probe error active Automatic On
E3Pb3 probe error active Automatic Ont, OFt HA1 HIGH temperature alarm active Auto
E2, dAt PAn Panic alarm not active Automatic ALd leak detector alarm not active Au
E10Clock alarm not active Automatic PA General pressure switch alarm not active Man
F1and QF2) · Motor overload protection terminals (QM1) Cleaning Do not use abrasiv
HA1Meaning HIGH temperature alarm, refers to probe LA1 LOW temperature alarm, refer
E4displayed · check probe type (H00) operating range · check the probe wiring? · p
E5displayed · check probe type (H00) · check the probe wiring E6 Pb6 probe error (
E6displayed · alarm icon permanently on · check the probe type · check the probe w
E7· measured values are outside operating range · label E7 displayed · alarm icon
AL1AH2 set in tA1. Value read by probe 1 · no effect on regulation · no effect on r
AL2Value read by probe 2 · recording of label AL2 in folder ALr · no effect on regu
Sources: becoolrefrigeration.co.uk, www.eliwell.com