Bell and Gossett E08
Power module temperature pump for 5 minutes and then If the problem continues, c
Source: e-90e__bego-e-90e-iom.pdf
What does Bell and Gossett E08 mean?
E08 signals that the power module (frequency converter / VFD section) inside the e-90E Smart Pump has reached its thermal protection limit. The drive's internal IGBT module temperature exceeded the safe operating threshold, forcing a shutdown to prevent permanent damage to the power electronics.
Symptoms
- Pump stops and displays E08 on the control panel.
- STATUS LED illuminates red steady.
- Drive enclosure is noticeably hot to the touch.
- Fault may recur quickly after restart if ambient temperature is not reduced.
Common causes
- High ambient air temperature around the drive enclosure.
- Restricted airflow preventing convective cooling of the drive.
- Drive operating at or near full load for extended periods in a warm environment.
- Internal cooling path blocked by accumulated dust or debris on the drive fins.
Diagnostic steps
- 01
Stop the pump and allow the drive to cool
Power down the pump and wait a minimum of 5 minutes. Allow the power module to cool to ambient before restarting — forced cooling with compressed air directed at drive fins is acceptable.
- 02
Check installation ambient temperature
Verify that the ambient air temperature at the drive location is within the specification on the motor data plate. Remove the pump from enclosed cabinets or recesses that trap heat if necessary.
- 03
Improve ventilation
Ensure adequate clearance around the drive enclosure. Remove any lagging, insulation, or enclosures restricting airflow. The drive relies on convective cooling and cannot tolerate restricted airspace.
- 04
Restart and monitor P13
After confirming ambient conditions are acceptable, restore power and restart. Monitor parameter P13 (Power Module Temperature) on the display to confirm the thermal reading is stabilizing at a safe level.
Keep this fix — get it by email with every Bell and Gossett error code
A clean printable version of this Bell and Gossett E08 guide + the full Bell and Gossett code pack (13 codes), straight to your inbox. Free.
When to call a professional
Contact a licensed technician if E08 persists in an environment within ambient temperature limits. A persistently overheating power module in normal conditions indicates failing IGBTs, a damaged internal heat sink, or a faulty thermal sensor — all requiring drive-level diagnosis and component replacement by qualified personnel.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Bell and Gossett error codes
Internal communication error code Description Cause Internal communication lost
E02E03 Motor overload error DC-bus overvoltage error · High motor current |Stop the
E04Rotor blocked External conditions cause the operation of the pump from generator
E05E06 EEPROM Data memory error Grid voltage error EEPROMData memory corrupted Volt
E07Motor winding temperature error [Motor thermal protection trip · the connection
E09Generic hardware error Hardware error temperature Stop the pump for 5 minutes an
E11LOW error Pressure sensor error Lack of water detection (if P48= Missing pressur
E12ERR) tank code sensor (not present in |connection cables ACT mode) Check the con
E14Description Low pressure error Cause Pressure below [(not present in ACT minimum
E15Loss of phase error One of the three power supply phases is missing (three- phas
E30E44 Multi-pump protocol error External analogue reference| External analogue pum
A03A05 A06 A15 A20 A30 A31 Description Derating Data memory alarm Cause Temperature
Sources: www.xylem.com