Traulsen Coil Sensor Open or Shorted
The Intela-Traul control reads the evaporator coil sensor as open or shorted.
Source: TRAULSEN/00213 Traulsen Intela-Traul Alarms Tech Bulletin TTB0013 (07-15).pdf
What does Traulsen Coil Sensor Open or Shorted mean?
This alarm indicates the controller cannot read a valid signal from the evaporator coil sensor because its circuit is open or shorted. The coil sensor is used for defrost termination and coil monitoring, so a bad reading can disrupt defrost behavior. A correct sensor reads about 32.7K ohms at 32F within ten percent.
Symptoms
- Alarm LED illuminated and horn sounding on the control
- Coil temperature reading missing or implausible
- Defrost cycles not terminating correctly
- Sensor resistance out of the expected range when tested
Common causes
- Coil sensor probe disconnected or loosely connected
- Open circuit in the coil sensor wiring
- Shorted coil sensor
- Failed coil sensor reading outside the 32.7K ohm range at 32F
Diagnostic steps
- 01
Locate the coil sensor
Gain access to the coil sensor inserted on the return-air side of the evaporator coil.
- 02
Check the connection
Confirm the coil sensor probe is properly connected and reconnect it if loose or disconnected.
- 03
Test sensor resistance
Disconnect the sensor and place the probe in ice water; at 32F resistance should read about 32.7K ohms plus or minus ten percent.
- 04
Replace a failed sensor
If resistance is outside that range, replace the coil sensor.
- 05
Confirm correct placement
On freezer models center the sensor about two inches from the top through the coil; on refrigerator models mount it on top of the coil.
Keep this fix — get it by email with every Traulsen error code
A clean printable version of this Traulsen Coil Sensor Open or Shorted guide + the full Traulsen code pack (11 codes), straight to your inbox. Free.
When to call a professional
Call a technician if reconnection does not clear the alarm or if you cannot meter the probe against the 32.7K-ohm spec. Coil-sensor placement differs between freezer and refrigerator models, and incorrect placement affects defrost termination. Accessing the evaporator coil, testing in an ice-water bath, and replacing the sensor are service tasks best handled by qualified personnel.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Traulsen error codes
Cabinet temperature has risen above the high-temperature alarm setpoint on the Intela-Traul control.
Low Temperature AlarmCabinet temperature has dropped below the low-temperature alarm setpoint on the Intela-Traul control.
Door Open AlarmThe Intela-Traul control detects a cabinet door open longer than the allowed time.
Power Loss AlarmThe Intela-Traul control detected an interruption of power to the unit.
System Leak AlarmThe Intela-Traul control detects a refrigeration system leak based on discharge-line temperature behavior.
CondenserClean AlarmThe Intela-Traul control signals that the condenser coil needs cleaning or that condenser airflow is restricted.
Cabinet Sensor Open or ShortedThe Intela-Traul control reads the cabinet air sensor as open or shorted.
Discharge Line Sensor Open or ShortedThe Intela-Traul control reads the discharge line sensor as open or shorted.
Liquid Line Sensor Open or ShortedThe Intela-Traul control reads the liquid line sensor as open or shorted.
Defrost Termination by TimeDefrost has terminated by time rather than by temperature for 72 hours on the Intela-Traul control.