Traulsen Liquid Line Sensor Open or Shorted
The Intela-Traul control reads the liquid line sensor as open or shorted.
Source: TRAULSEN/00213 Traulsen Intela-Traul Alarms Tech Bulletin TTB0013 (07-15).pdf
What does Traulsen Liquid Line Sensor Open or Shorted mean?
This alarm means the controller cannot read a valid signal from the liquid line sensor because its circuit is open or shorted. The liquid line temperature is monitored on Smart Control units and contributes to liquid-line and shutdown alarm logic, so an invalid reading must be corrected for the control to protect the system properly.
Symptoms
- Alarm LED illuminated and horn sounding on the control
- Liquid line temperature reading missing or implausible
- Liquid line or shutdown alarm status behaving unexpectedly
- Sensor resistance out of the expected range when tested
Common causes
- Liquid line sensor probe disconnected or loosely connected
- Open circuit in the liquid line sensor wiring
- Shorted liquid line sensor
- Failed liquid line sensor reading outside the expected range
Diagnostic steps
- 01
Locate the liquid line sensor
Access the liquid line sensor on the refrigeration circuit per the unit's service documentation.
- 02
Check the connection
Confirm the liquid line probe is properly connected and reconnect it if loose or disconnected.
- 03
Test sensor resistance
Disconnect the sensor and verify resistance against the Intela-Traul sensor spec of about 32.7K ohms at 32F plus or minus ten percent.
- 04
Replace a failed sensor
If resistance is outside the expected range, replace the liquid line sensor.
- 05
Confirm alarm clears
After reconnection or replacement, verify the liquid line alarm status returns to normal on the control.
Keep this fix — get it by email with every Traulsen error code
A clean printable version of this Traulsen Liquid Line Sensor Open or Shorted guide + the full Traulsen code pack (11 codes), straight to your inbox. Free.
When to call a professional
Call a technician if reconnecting the probe does not clear the alarm or if you cannot meter the sensor against spec. The liquid line sensor feeds liquid-line and shutdown alarm logic, so a wrong reading can mask a real sealed-system problem. Testing and replacing refrigeration-circuit sensors are service tasks best handled by qualified personnel.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Traulsen error codes
Cabinet temperature has risen above the high-temperature alarm setpoint on the Intela-Traul control.
Low Temperature AlarmCabinet temperature has dropped below the low-temperature alarm setpoint on the Intela-Traul control.
Door Open AlarmThe Intela-Traul control detects a cabinet door open longer than the allowed time.
Power Loss AlarmThe Intela-Traul control detected an interruption of power to the unit.
System Leak AlarmThe Intela-Traul control detects a refrigeration system leak based on discharge-line temperature behavior.
CondenserClean AlarmThe Intela-Traul control signals that the condenser coil needs cleaning or that condenser airflow is restricted.
Cabinet Sensor Open or ShortedThe Intela-Traul control reads the cabinet air sensor as open or shorted.
Coil Sensor Open or ShortedThe Intela-Traul control reads the evaporator coil sensor as open or shorted.
Discharge Line Sensor Open or ShortedThe Intela-Traul control reads the discharge line sensor as open or shorted.
Defrost Termination by TimeDefrost has terminated by time rather than by temperature for 72 hours on the Intela-Traul control.