Traulsen Discharge Line Sensor Open or Shorted

The Intela-Traul control reads the discharge line sensor as open or shorted.

Source: TRAULSEN/00213 Traulsen Intela-Traul Alarms Tech Bulletin TTB0013 (07-15).pdf

Want this fix in your inbox? Full Discharge Line Sensor Open or Shorted guide + every Traulsen code, printable, free.

What does Traulsen Discharge Line Sensor Open or Shorted mean?

This alarm means the controller cannot read a valid signal from the discharge line sensor because its circuit is open or shorted. The discharge sensor monitors hot-gas temperature near the compressor and feeds the system leak detection logic, so a faulty probe can both trigger this alarm and interfere with leak detection. A correct sensor reads about 32.7K ohms at 32F within ten percent.

Symptoms

  • Alarm LED illuminated and horn sounding on the control
  • Discharge temperature reading missing or implausible
  • System leak detection behaving unexpectedly
  • Sensor resistance out of the expected range when tested

Common causes

  • Discharge line sensor probe disconnected or loosely connected
  • Open circuit in the discharge sensor wiring
  • Shorted discharge line sensor
  • Dislocated or uninsulated probe, or a failed sensor outside the 32.7K ohm range at 32F

Diagnostic steps

  1. 01

    Locate the discharge sensor

    Access the discharge sensor mounted on the hot-gas side of the compressor (R and A Series).

  2. 02

    Check the connection

    Confirm the discharge probe is properly connected and reconnect it if loose.

  3. 03

    Test sensor resistance

    Disconnect the sensor and place the probe in ice water; at 32F resistance should read about 32.7K ohms plus or minus ten percent.

  4. 04

    Verify placement and insulation

    Ensure the probe sits close to the compressor before the hot-gas loop and is insulated as required.

  5. 05

    Replace a failed sensor

    If resistance is out of range or the probe is damaged, replace the discharge line sensor.

Keep this fix — get it by email with every Traulsen error code

A clean printable version of this Traulsen Discharge Line Sensor Open or Shorted guide + the full Traulsen code pack (11 codes), straight to your inbox. Free.

I am a — required, one click

When to call a professional

Call a technician if reconnecting and re-placing the probe does not clear the alarm. The discharge sensor must be positioned near the compressor before the hot-gas loop and insulated; getting this wrong skews leak detection. Testing the probe against the 32.7K-ohm spec and replacing it are service tasks that should be done by qualified personnel.